The Honeywell SAI-1620M is a safe high-density analog input module designed for the Honeywell Safety Manager safety instrumented system (SIS).
It provides 16 analog input channels for acquiring process signals used in safety monitoring and control applications. The module features 12-bit analog-to-digital conversion and is designed for safety-related applications up to SIL 3 in accordance with IEC 61508.
Important model identification: Honeywell's hardware reference lists the module variants as FS-SAI-1620m, FC-SAI-1620m, and FA-SAI-1620m. The SAI-1620m module accepts voltage signals in the 0–4.1 V range. Field current signals such as 4–20 mA require a compatible termination assembly or signal converter.
|
Parameter |
Specification |
|---|---|
|
Manufacturer |
Honeywell |
|
Model |
SAI-1620M |
|
Product Series |
Safety Manager |
|
Product Type |
Safe High-Density Analog Input Module |
|
Number of Channels |
16 |
|
Input Signal Range |
0–4.1 VDC |
|
Input Resistance |
Greater than 1 MΩ |
|
A/D Converter |
12-bit |
|
A/D Converter Inaccuracy |
±1 LSB |
|
Module Inaccuracy |
Less than 0.25% |
|
Maximum Input Signal |
±36 VDC |
|
Maximum Load Capacitance |
100 nF |
|
Channel Crosstalk |
Greater than 60 dB |
|
Power Supply |
5 VDC, 35 mA; 24 VDC, 35 mA |
|
Space Requirement |
4 TE × 3 HE (4 HP × 3U) |
|
Safety Classification |
SIL 3 application capability |
|
Approvals |
CE, TÜV, UL, CSA, FM |
16-Channel Input: Supports multiple analog measurement points in one compact module.
Safety-Critical Design: Intended for high-integrity safety applications in Honeywell Safety Manager systems.
12-Bit Resolution: Provides digital conversion of analog input signals.
High Input Impedance: Input resistance greater than 1 MΩ.
Built-In Diagnostics: Supports system-controlled self-testing of measurement accuracy and internal operating conditions.
Flexible Signal Interface: Can be used with compatible field termination assemblies and signal conversion modules.
Compact Installation: Designed for installation in the Honeywell Safety Manager I/O chassis.
Safety instrumented systems (SIS)
Industrial process monitoring
Chemical and petrochemical plants
Oil and gas facilities
Power generation plants
Pressure, temperature, and flow monitoring
Emergency shutdown and safety protection systems
Confirm the exact module variant and hardware revision before installation.
Do not connect a 4–20 mA field signal directly to the 0–4.1 V input without a compatible signal conversion arrangement.
Use compatible termination assemblies such as TSAI-1620m or approved conversion modules.
Check chassis connector coding and system compatibility.
Follow Honeywell wiring diagrams and safety procedures during installation.
Verify channel configuration and perform the required system diagnostics after replacement.