Email Us justwellautomation@qq.com
HONEYWELL FT6961-18 Control System Component
Item NO.:
FT6961-18Payment:
T/TPrice:
$1280Product Origin:
USAColor:
NEWProduct weight:
0.35kgLead Time:
In stockWe will arrange delivery within 3-5 days after receiving the payment.
Our express delivery: DHL and FedEx.
Quality packing for each product
Destination country all taxes & duty to be paid by buyer
Only part of the brand and model, if you have other product needs, please contact us.
Correction: The Honeywell FT6961-18 is not a generic control system component. It is a Single-Stage Frost Protection Thermostat from the Honeywell FT69 series.
It is designed to protect air handling units, ventilation systems and heat exchangers from freezing. The thermostat uses a gas-filled copper capillary sensor to detect low temperatures and activate its switching contacts when the temperature falls below the preset threshold.
The FT6961-18 features a 1.8-meter capillary tube and automatic reset functionality.
|
Parameter |
Description |
|---|---|
|
Brand |
Honeywell |
|
Model |
FT6961-18 |
|
Product Series |
FT69 |
|
Product Type |
Frost Protection Thermostat |
|
Operating Principle |
Gas-filled capillary sensor |
|
Temperature Setting Range |
-8 to +8°C |
|
Capillary Length |
1.8 m |
|
Sensor |
Copper capillary with sensing bulb |
|
Reset Type |
Automatic Reset |
|
Switching Contact |
SPDT |
|
Switching Capacity |
24–250 VAC, 16(8) A |
|
Hysteresis |
2 K |
|
Reproducibility |
±1 K |
|
Operating Temperature |
-20 to +55°C |
|
Protection Rating |
IP65 |
|
Housing Material |
ABS and Polycarbonate |
|
Dimensions |
140 × 62 × 65 mm |
|
Weight |
Approx. 320 g |
Automatic Reset: Automatically restores operation when the temperature returns to a safe level.
Capillary Temperature Sensing: Monitors temperature along the capillary sensing element.
Frost Protection: Helps prevent freezing damage to heating coils and heat exchangers.
Reliable Switching: Mechanical microswitch with SPDT contacts.
IP65 Protection: Dust-tight and protected against water jets.
Easy Installation: Includes a compact housing and flexible capillary tube.
HVAC air handling units
Ventilation and air conditioning systems
Air heating coil protection
Heat exchanger frost protection
Refrigeration and cooling systems
Electric heating control
Temperature-related alarm systems
Install the capillary tube evenly across the air stream.
Ensure the sensing element is not damaged or sharply bent.
Maintain at least 30 cm of cooling length for the capillary coil.
Verify the electrical contact rating before connecting loads.
Install according to the manufacturer's wiring instructions.
Confirm automatic reset operation during commissioning.
Reliable low-temperature protection
Automatic reset design
1.8-meter capillary sensing element
Suitable for HVAC and industrial climate control
IP65-rated enclosure
Simple installation and maintenance