Email Us justwellautomation@qq.com
HONEYWELL ML7421B8012-E Valve Actuator
Item NO.:
ML7421B8012-EPayment:
T/TPrice:
$1280Product Origin:
USAColor:
NEWProduct weight:
0.35kgLead Time:
In stockWe will arrange delivery within 3-5 days after receiving the payment.
Our express delivery: DHL and FedEx.
Quality packing for each product
Destination country all taxes & duty to be paid by buyer
Only part of the brand and model, if you have other product needs, please contact us..
The Honeywell ML7421B8012-E is a non-spring-return electric linear valve actuator designed for modulating control of Honeywell globe valves in HVAC and building automation systems.
It receives an analog control signal and adjusts the valve stem position to regulate hot water, chilled water, and other fluid flows.
It features a 38 mm stroke and a nominal stem force of 1,800 N.
|
Parameter |
Specification |
|---|---|
|
Brand |
Honeywell |
|
Model |
ML7421B8012-E |
|
Product Type |
Electric Linear Valve Actuator |
|
Control Type |
Modulating |
|
Power Supply |
24 VAC ±15%, 50/60 Hz |
|
Power Consumption |
14 VA |
|
Control Signal |
0–10 VDC / 2–10 VDC |
|
Current Signal |
0–20 mA / 4–20 mA, selectable |
|
Position Feedback |
2–10 VDC |
|
Stroke |
38 mm |
|
Nominal Stem Force |
1,800 N |
|
Running Time |
Approx. 3.5 minutes at 50 Hz |
|
Spring Return |
No |
|
Protection Rating |
IP54 |
|
Insulation Class |
Class II |
|
Operating Temperature |
-10 to +50°C |
|
Storage Temperature |
-40 to +70°C |
|
Weight |
Approx. 2.0–2.3 kg |
38 mm linear actuator stroke.
High output force of 1,800 N.
Selectable voltage or current control signals.
2–10 VDC position feedback.
Adjustable direct or reverse acting operation.
Automatic stroke adaptation.
Manual operation knob for maintenance.
Force-limiting end stops.
Maintenance-free synchronous motor design.
HVAC heating and cooling systems
Chilled-water control
Hot-water circulation systems
Commercial building automation
Air-conditioning systems
Industrial fluid-flow regulation
Globe valve position control
Confirm compatibility with the valve body and required 38 mm stroke.
Use a 24 VAC power supply within the specified voltage range.
Configure the correct input signal type before operation.
Check direct/reverse acting settings.
Ensure the actuator is correctly mounted and aligned with the valve stem.
This is a non-spring-return actuator; it does not automatically return to a safe position after power failure.