HONEYWELL FC-IOCHAS-0003R Safety Manager I/O Chassis
Item NO.:
FC-IOCHAS-0003RPayment:
T/TPrice:
$1280Product Origin:
USAColor:
NEWProduct weight:
0.35kgLead Time:
In stockWe will arrange delivery within 3-5 days after receiving the payment.
Our express delivery: DHL and FedEx.
Quality packing for each product
Destination country all taxes & duty to be paid by buyer
Only part of the brand and model, if you have other product needs, please contact us.
The Honeywell FC-IOCHAS-0003R is a redundant I/O chassis designed for the Honeywell Safety Manager safety control system.
It provides the mechanical housing, backplane connections, and module installation structure for redundant I/O modules. The chassis accommodates up to 9 pairs of redundant I/O modules (18 modules in total), supporting high-availability safety and process control applications.
The chassis includes an industrial 19-inch housing, two IO-0001 extender modules, and a blind front assembly. Honeywell identifies the IOCHAS-0003R as a replacement for the older IOCHAS-0001R chassis.
|
Parameter |
Specification |
|---|---|
|
Manufacturer |
Honeywell |
|
Model |
FC-IOCHAS-0003R |
|
Product Series |
Safety Manager |
|
Product Type |
Redundant I/O Chassis |
|
Chassis Configuration |
Redundant |
|
Maximum I/O Capacity |
18 I/O modules |
|
Redundant Configuration |
Up to 9 pairs |
|
Housing |
Industrial metal enclosure |
|
Rack Format |
19-inch |
|
Included Extenders |
2 × IO-0001 |
|
Backplane |
Redundant I/O backplane |
|
5V-1 Power Consumption |
35 mA |
|
5V-2 Power Consumption |
35 mA |
|
Width |
482.6 mm |
|
Depth |
280 mm |
|
Height |
4 HE for subsequent chassis; first chassis uses additional mounting space |
|
Weight |
Approximately 8.5 kg |
|
Approvals |
CE, UL, CSA, TÜV, FM |
Redundant I/O Architecture: Supports up to nine pairs of redundant I/O modules.
High System Availability: Designed for applications where continuous operation and fault tolerance are important.
High-Density Installation: Accommodates up to 18 I/O modules in a standard 19-inch chassis.
Integrated Backplane: Provides the electrical interconnection between installed I/O modules.
I/O Extender Modules: Includes two IO-0001 extender modules for chassis integration.
Industrial Construction: Designed for installation in industrial control cabinets.
Legacy System Replacement: Provides a replacement option for the older IOCHAS-0001R chassis, subject to configuration compatibility.
Honeywell Safety Manager systems
Safety Instrumented Systems (SIS)
Emergency Shutdown (ESD) systems
Oil and gas processing facilities
Petrochemical plants
Power generation facilities
Industrial process safety monitoring
Confirm that the existing system uses the Honeywell Safety Manager redundant I/O architecture.
Verify chassis revision and backplane compatibility before replacement.
Check that the required IO-0001 extender modules are included.
Confirm compatibility of all installed I/O modules and associated termination assemblies.
Follow Honeywell installation instructions for chassis mounting and electrical connections.
Observe ESD precautions and isolate power before installation or maintenance.
Do not confuse this redundant chassis with the non-redundant IOCHAS-0003S version.