The Honeywell DPS400 is an adjustable differential pressure switch designed for air conditioning, ventilation, and HVAC systems. It monitors pressure differences between two points and activates an electrical switching contact when the preset pressure threshold is reached.
It is commonly used to monitor air filters, fans, airflow, and ventilation equipment, helping detect clogged filters and airflow failures.
|
Parameter |
Specification |
|---|---|
|
Brand |
Honeywell |
|
Model |
DPS400 |
|
Product Name |
Differential Pressure Switch |
|
Product Series |
DPS Series |
|
Product Type |
Air Differential Pressure Switch |
|
Pressure Adjustment Range |
40–400 Pa |
|
Switching Differential |
20 Pa |
|
Pressure Medium |
Air and non-aggressive gases |
|
Maximum Operating Pressure |
10 kPa |
|
Switching Contact |
SPDT |
|
Contact Capacity |
1.5 A / 250 VAC |
|
Pressure Connections |
2 × 6 mm hose connections |
|
Electrical Connection |
AMP 6.3 × 0.8 mm / Screw Terminals |
|
Protection Rating |
IP54 |
|
Diaphragm Material |
Silicone |
|
Operating Temperature |
-20 to +85°C |
|
Storage Temperature |
-40 to +85°C |
|
Mounting Type |
Wall / Panel Mounting |
Adjustable Pressure Setting: Adjustable switching point from 40 to 400 Pa.
Differential Pressure Monitoring: Detects pressure differences between two air pressure points.
SPDT Contact: Provides normally open and normally closed switching contacts.
Filter Monitoring: Detects clogged or dirty air filters.
Airflow Detection: Monitors fan and ventilation system operation.
Compact Design: Easy installation in HVAC control systems.
Reliable Construction: Silicone diaphragm provides dependable pressure sensing.
Easy Adjustment: Integrated scale allows convenient pressure setting.
HVAC systems
Air conditioning equipment
Ventilation systems
Air filter blockage monitoring
Industrial air handling units
Fan and blower monitoring
Fire damper monitoring
Building automation systems
Connect the high-pressure and low-pressure ports correctly.
Verify the pressure adjustment range before installation.
Use compatible pressure hoses with the specified diameter.
Ensure electrical connections match the SPDT contact configuration.
Avoid exceeding the maximum operating pressure.
Do not use with aggressive gases or unsuitable liquids.
Install according to the manufacturer's mounting instructions.
Genuine Honeywell HVAC control component.
Adjustable 40–400 Pa pressure range.
SPDT switching contact.
Reliable air pressure differential monitoring.
Suitable for filter, fan, and airflow monitoring.