HONEYWELL 8C-PAIMA1 Universal Analog Input Module
Item NO.:
8C-PAIMA1Payment:
T/TPrice:
$1280Product Origin:
USAColor:
NEWProduct weight:
0.35kgLead Time:
In stockWe will arrange delivery within 3-5 days after receiving the payment.
Our express delivery: DHL and FedEx.
Quality packing for each product
Destination country all taxes & duty to be paid by buyer
Only part of the brand and model, if you have other product needs, please contact us..
The Honeywell 8C-PAIMA1 is a Series 8 low-level analog temperature input module designed for Honeywell Experion PKS control systems.
Correction: Although sometimes described as a universal analog input module, its specific function is temperature measurement. It accepts thermocouple (TC) and RTD sensor signals and converts them into digital process values for the controller.
|
Parameter |
Specification |
|---|---|
|
Brand |
Honeywell |
|
Model |
8C-PAIMA1 |
|
Product Type |
Low-Level Analog Temperature Input Module |
|
System |
Experion PKS Series 8 |
|
Input Channels |
16 |
|
Input Types |
Thermocouple and RTD |
|
Supply Voltage |
24 VDC |
|
Module Current |
120 mA |
|
Thermocouple Input Range |
-20 to +100 mV |
|
Input Scan Rate |
1 second |
|
Channel Bandwidth |
0–4.7 Hz (-3 dB) |
|
Maximum Gain Error |
0.05% of full scale |
|
Channel Isolation |
Fully isolated |
|
Operating Temperature |
0 to 60°C |
|
Storage Temperature |
-40 to +85°C |
|
Compatible IOTA |
8C-TAIMA1 |
|
Coating |
Conformal-coated |
Supports 16 thermocouple and RTD input channels.
Fully isolated input channels for improved signal integrity.
Integrated cold-junction compensation for thermocouple measurements.
Configurable open-thermocouple detection.
Accurate temperature signal acquisition.
Supports module removal and insertion under power.
Conformal coating for improved environmental protection.
Industrial temperature monitoring
Chemical and petrochemical plants
Oil and gas processing
Power generation
Furnace and boiler temperature measurement
Industrial process automation
Designed for Honeywell Series 8 I/O systems.
Requires a compatible 8C-TAIMA1 IOTA termination assembly.
Confirm thermocouple or RTD sensor type and configuration before wiring.
Check channel isolation and sensor wiring requirements.
Verify module and IOTA compatibility before replacement.