General Information
- Manufacturer: Honeywell Analytics
- Order number: 05701-A-0302
- Product type: System 57 / 5701 single channel control card, catalytic sensor version
- Sensor drive: Factory fitted catalytic Sensor Drive Module 05701-A-0284
- System: Rack-mounted System 57 gas detection control system
- Function: Sensor signal processing, front-panel display, alarm comparison, fault supervision and channel status indication
- Configuration: Microprocessor controlled, setup stored in EEPROM
- Optional module: Analogue Output Module 05701-A-0285, isolated 0 to 20 mA or 4 to 20 mA loop
- Related card: 05701-A-0301 is the 4 to 20 mA version; this 0302 version is for catalytic LEL sensors
- Installation: Euro-rack card mounted in the System 57 rack with backplane connection
Key Specifications
- DC supply: 18 to 32 VDC
- Power consumption: 3.75 W typical, including catalytic sensor
- Sensor type: Catalytic combustible LEL bridge sensor, bridge drive at 200 mA
- Display: 25-segment analog bar, four-character digital display, four-character message display, power on and card select icons
- Alarm LEDs: A1, A2, A3 red gas alarm LEDs; Fault and Inhibit amber LEDs
- Front push-button: Alarm reset and card select
- Alarm setpoint resolution: 1% fsd steps
- Linearity: ±1% fsd
- Repeatability: ±1% fsd
- Electronic drift: Less than ±2% over 6 months
- Remote inputs: RESET and INHIBIT, each configurable active high or active low
- Remote input switching level: Approx. +2 V relative to system 0 V
- Remote input drive current: Less than 5 mA
- Remote input maximum voltage: 32 V
- Optional analogue output: Isolated current loop, 0 to 20 mA or 4 to 20 mA, loop voltage up to 40 V
- Relay outputs: Provided by separate Field Interface or Relay Cards; contact rating 5 A at 110/250 VAC non-inductive, 5 A at 32 VDC non-inductive
- Field terminal cross section: Up to 2.5 mm², 14 AWG
- Card dimensions: Height 112 mm, width 25 mm, depth 170 mm
- Card weight: Approx. 165 g, supplier data
- Operating temperature: -5 to +55 °C
- Storage temperature: -25 to +55 °C
- Humidity: 0 to 90% RH, non-condensing
- EMC: EN50270 per System 57 product data
Features and Advantages
- Single channel control for one catalytic combustible gas detector with dedicated bridge drive and signal conditioning
- Front panel analog bar and digital message display show live reading and channel status at a glance
- Three configurable A1, A2 and A3 alarm levels support staged gas warning and alarm strategies
- Fault supervision detects sensor hardware failure, out-of-limits signal, card hardware or software fault
- Inhibit mode can be applied locally, remotely or automatically during start-up and engineering functions
- EEPROM retains channel configuration, alarm setpoints and calibration data after power off
- Self-validation checks circuit components, software operation and backplane communications
- Optional isolated analogue output transmits the live reading to recorders, PLCs or remote monitoring systems
- Remote reset and inhibit inputs integrate the channel into plant safety and maintenance procedures
- Card-based rack design allows channel replacement and system expansion within the System 57 cabinet
- Sensor drive module and control card are matched at factory for catalytic sensor compatibility
- Clear LED and message diagnostics speed up commissioning, calibration and troubleshooting
Typical Applications
- Combustible LEL gas detection in oil and gas processing plants
- Chemical and petrochemical storage, pumping and processing areas
- Refineries, tank farms and compressor stations
- Painting, coating and solvent vapor areas
- Power generation, turbine rooms and fuel storage zones
- Industrial boiler rooms, heating plant and combustion equipment monitoring
- System 57 based fixed gas detection panels requiring catalytic sensor channel control
- Hazardous area plant monitoring with sensors located in the field and control cards mounted in the cabinet