Schneider/Magnecraft KR-11DGE-24 — General Purpose Hermetic Relay
Specifications
表格
| Item |
Details |
| Order code |
KR-11DGE-24 (also referenced as 750XBXH-24D / KR11DGE-24) |
| Relay type |
Hermetically sealed general-purpose plug-in relay |
| Contact configuration |
2 C/O, DPDT, 8-pin termination |
| Contact material |
Silver cadmium oxide |
| Contact rating |
10 A at 240 V AC; common listed control rating 3 A at 277 V AC, verify load class |
| Coil voltage |
24 V DC |
| Coil resistance |
472 Ω |
| Nominal coil power |
Approx. 1.2 W DC |
| Operate time |
Approx. 15 ms |
| Release time |
Approx. 10 ms |
| Dielectric strength |
1.5 kV AC, coil-to-contact |
| Mechanical life |
Approx. 10 × 10⁷ operations |
| Operating temperature |
-45 … +70 °C |
| Termination |
8-pin plug-in, fits compatible DIN rail socket |
| Housing dimensions H × W × D |
Approx. 52 × 39 × 33 mm |
| Approvals |
UL, CSA per distributor data |
| Optional socket/clips |
Matching 70-750D11-11 DIN socket and retaining clip listed by supplier |
Features and Advantages
- Hermetic sealing protects internal contacts and coil against dust, moisture and corrosive atmospheres.
- DPDT changeover contacts support two independent switching or signal circuits.
- 24 V DC coil suits PLC outputs, control panels and low-voltage logic circuits.
- Fast operate/release times suit general-purpose relay logic and signal switching.
- Plug-in 8-pin construction simplifies replacement and maintenance with a compatible socket.
- Wide -45 … +70 °C operating range supports demanding industrial environments.
- High mechanical life supports repeated switching in control and alarm circuits.
Applications
- PLC output relay expansion and control-circuit interlocking
- Alarm, status, indicator and signal relay functions
- Small loads, contactors and auxiliary solenoid control in cabinet panels
- Humid, dusty or mildly corrosive industrial locations requiring sealed contacts
- Replacement service for legacy Magnecraft/P&B/Schneider relay sockets
Installation and Usage Notes
- Confirm contact rating, AC/DC load class and minimum load before switching motors, lamps or inductive loads.
- Use the manufacturer-matched 8-pin socket and retaining clip; socket rating may limit overall relay capacity.
- Observe coil polarity for the DC coil and provide surge suppression where inductive loads are switched.
- Do not exceed 10 A at 240 V AC or other listed contact limits; derate for DC and inductive loads.
- Verify UL/CSA certification and hazardous-location suitability for the actual destination and installation zone.
- Check replacement compatibility with the existing socket wiring diagram before removing the relay.
- Silver-cadmium-oxide contacts require normal minimum load; very light signal-level loads may need contact rating confirmation.