chneider Electric A9F74116 — Acti9 iC60N Miniature Circuit Breaker
A 1-pole, 16 A, C-curve thermal-magnetic miniature circuit breaker (MCB) from the Schneider Acti9 iC60N range, designed for overload and short-circuit protection of industrial and commercial low-voltage distribution circuits.
Key Technical Specifications
表格
| Item |
Specification |
| Product range |
Acti9 iC60N |
| Catalog number |
A9F74116 |
| Device type |
Miniature circuit breaker (MCB) |
| Number of poles |
1P (1 protected pole) |
| Rated current (In) |
16 A |
| Trip curve |
C (magnetic trip 5 … 10 In) |
| Rated operational voltage (Ue) |
230 / 400 V AC (1P); up to 230 V on the protected pole |
| Rated insulation voltage (Ui) |
500 V AC |
| Rated impulse voltage (Uimp) |
6 kV |
| Breaking capacity |
6 kA at 230/240 V AC (IEC/EN 60898-1); 10 kA at 220–240 V AC (IEC/EN 60947-2) |
| Frequency |
50/60 Hz |
| Tripping technology |
Thermal-magnetic (bimetal + solenoid) |
| Isolation |
Suitable as industrial isolator per IEC/EN 60947-2 |
| Usage category |
AC / DC |
| Overvoltage category |
III |
| Pollution degree |
3 |
| Mounting |
35 mm DIN rail (EN 60715) |
| Connection |
Screw terminals, up to 25 mm² |
| Width |
1 module (18 mm) |
| Standards |
IEC/EN 60898-1, IEC/EN 60947-2 |
| Accessories |
Plug-in auxiliary contacts, shunt undervoltage releases, Vigi residual-current modules |
Advantages & Features
- Dual breaking rating — 6 kA to IEC 60898-1 (residential/commercial) and 10 kA to IEC 60947-2 (industrial), covering both distribution and industrial panels.
- C-curve tripping — 5–10 In magnetic trip suits general-purpose loads with moderate inrush (lighting, sockets, control circuits, small motors), avoiding nuisance trips while still clearing faults fast.
- VisiSafe — integrated terminal shutter and visible load-side isolation improve safety during wiring and maintenance.
- Visitrip — clear trip indication identifies the faulty outgoing circuit at a glance, reducing fault-finding time.
- Modular Acti9 ecosystem — plug in auxiliary contacts, OF/SD, shunt trips and Vigi RCBO attachments on the side, no tools needed.
- Compact 18 mm width — one module per pole maximizes circuits per panel.
- Industrial-grade isolation rating — certified as a disconnection device per IEC/EN 60947-2, suitable for service-entrance and isolation duties.
- RoHS-compliant, long service life — part of Schneider's flagship Acti9 line with global availability and long-term support.
Typical Applications
- Branch-circuit protection in commercial and industrial distribution boards
- Lighting, socket-outlet and small-power final circuits
- Control panels, PLC cabinets and automation system supply protection
- HVAC, pumps, fans and small motor branch circuits (with appropriate overload coordination)
- Hotel, office, hospital and retail building electrical distribution
- OEM machine builders and panel builders using Acti9 / Prisma E / Set enclosures
- DC auxiliary circuits where AC/DC-rated MCBs are required
Notes / Considerations
- 1P only — protects the line conductor; the neutral is not switched. For 1P+N or 2P protection, choose A9F74616 (1P+N) or A9F75216 (2P).
- C-curve is not for high-inrush motor circuits — for direct-on-line motors, use a D-curve MCB or a dedicated motor-protective circuit breaker (GV2/GV3).
- Verify available fault current at the panel does not exceed the applicable breaking rating (6 kA per IEC 60898-1 for typical building use).
- For earth-leakage / residual-current protection, add a Vigi iC60 or pair with an RCCB upstream — this MCB alone does not provide shock protection.
- Torque line/load conductors to the recommended value (≈ 2.5 Nm); do not exceed 25 mm² per terminal.
- Use only Schneider-approved Acti9 accessories; third-party add-ons may void the listing.
- Always de-energize upstream supply before working on the breaker; VisiSafe provides terminal protection but does not replace lockout/tagout.
- For DC circuits, confirm the DC voltage and pole arrangement against the datasheet — DC breaking is lower than AC and may require series-pole use.