SCHNEIDER A9F84216 Acti9 Miniature Circuit Breaker
Item NO.:
A9F84216Payment:
T/TPrice:
$650Product Origin:
JapanColor:
NEWProduct weight:
0.21KGLead Time:
In stockWe will arrange delivery within 3-5 days after receiving the payment.
Our express delivery: DHL and FedEx.
Quality packing for each product
Destination country all taxes & duty to be paid by buyer
Only part of the brand and model, if you have other product needs, please contact us.
The Schneider Electric A9F84216 is an Acti9 iC60H miniature circuit breaker (MCB) designed to protect low-voltage electrical circuits against overloads and short circuits.
It features a two-pole configuration, 16A rated current, and C-curve thermal-magnetic tripping technology. With a high breaking capacity, it is suitable for industrial and commercial electrical distribution systems.
|
Parameter |
Specification |
|---|---|
|
Brand |
Schneider Electric |
|
Model |
A9F84216 |
|
Product Series |
Acti9 iC60 |
|
Device Type |
Miniature Circuit Breaker (MCB) |
|
Device Short Name |
iC60H |
|
Number of Poles |
2P |
|
Protected Poles |
2 |
|
Rated Current |
16 A |
|
Tripping Curve |
C Curve |
|
Trip Technology |
Thermal-Magnetic |
|
Rated Operational Voltage |
400 V AC |
|
Network Frequency |
50/60 Hz |
|
Breaking Capacity (Icn) |
10 kA at 400 V AC |
|
Breaking Capacity (Icu) |
15 kA at 380–415 V AC |
|
Breaking Capacity (Icu) |
30 kA at 220–240 V AC |
|
DC Breaking Capacity |
15 kA at ≤125 V DC |
|
Rated Insulation Voltage |
500 V AC |
|
Impulse Withstand Voltage |
6 kV |
|
Magnetic Tripping Limit |
8 × In ±20% |
|
Mounting |
35 mm DIN Rail |
|
Standards |
IEC/EN 60898-1, IEC/EN 60947-2 |
Two-pole protection: Provides simultaneous protection and isolation of two conductors.
Overload protection: Thermal tripping helps prevent damage caused by excessive current.
Short-circuit protection: Magnetic tripping provides rapid circuit interruption during faults.
C-curve characteristics: Suitable for circuits with moderate inrush currents.
High breaking capacity: Provides reliable fault interruption in industrial distribution systems.
VisiTrip indication: Helps identify faulty circuits quickly.
VisiSafe indication: Provides visual confirmation of contact separation.
DIN rail mounting: Allows convenient installation in electrical control panels.
Industrial electrical distribution panels
Control cabinets and automation systems
Commercial building electrical installations
Lighting and power distribution circuits
Machinery and equipment protection
Industrial control circuits
Verify rated current, voltage, and breaking capacity before installation.
Confirm that the two-pole configuration matches the electrical circuit.
Check wiring connections and terminal tightening torque.
Ensure the prospective short-circuit current does not exceed the breaker's rated capacity.
Install on a compatible DIN rail.
Installation and maintenance should be performed by qualified electrical personnel.
Disconnect the power supply before installation or maintenance.